A

The Building Regulations 2000

Structure

APPROVED DOCUMENT

A1 Loading

A2 Ground movement

A3 Disproportionate collapse

2004 EDITION

MAIN CHANGES IN THE 2004

EDITION

This edition of Approved Document A,

Structure, replaces the 1992 Edition (with 1994

and 2000 amendments edition). The main

changes are:

Use of Guidance

a. Eurocodes: an announcement is given

regarding the forthcoming introduction of

the Structural Eurocodes and their

National Annexes.

b. House construction: reference is made

to the intended publication of guidance

by industry of alternative forms of house

construction to that of traditional

masonry.

A1 and A2

Traditional dwellings

c. The guidance on the sizing of timber

floors and roofs for traditional house

construction has been removed as the

Timber Tables are now published by

TRADA. However, the TRADA Tables are

referenced under Section 2B.

d. A revised map of basic wind speeds in

accordance with BS6399:Part 2 replaces

the superseded map which was based on

BS CP3 Chapter V.

e. Stainless steel cavity wall ties have been

specified to all houses regardless of their

location.

f. The guidance on masonry walls to

dwellings has been extended to enable

the rules to be applicable when using

either the appropriate British Standards

or the emerging BS EN CEN Standards.

g. The guidance on concrete foundations to

houses has been revised to align with the

recommendations given in the British

Standards and other authoritative

guidance. Recommendations on minimum

foundation depths have also been

included to counter the impact of

predicted climate changes.

h. The guidance on the design and

construction of domestic garages has

been extensively updated to reflect

modern practice.

A3

i. Disproportionate collapse: the

Application Limit to the Requirement (ie.

the 5 storey limit) has been removed so

as to bring all buildings under control of

the A3 Requirement.

The modified guidance has been

developed from commissioned research

and consideration of the

recommendations given in the

forthcoming Eurocode EN1991-1-7 on

Accidental Actions.

Structure Approved Document A

PAGE

Use of Guidance 3

Loading and Ground Movement 5

The Requirements 5

Guidance 6

Introduction 6

Section 1: Codes, Standards and other

references for all building types 7

Loading 7

Structural work of timber 7

Structural work of masonry 7

Structural work of reinforced, pre-stressed

or plain concrete 7

Structural work of steel 7

Structural work of aluminium 7

Foundations 7

Ground Movement (Requirement A2(b) 8

Existing buildings 8

Section 2: Sizes of structural elements

for certain residential buildings and

other small buildings of traditional

construction 9

General 9

Definitions 9

Section 2A: Basic requirements for

stability 10

Section 2B: Sizes of certain timber

members in floors and roofs for

dwellings. Areas at risk from House

Longhorn Beetle 11

Sizing of members 11

House Longhorn Beetle 11

Section 2C: Thickness of walls in

certain small buildings 12

Application 12

Wall types 12

The use of this section 12

Conditions relating to the building of

which the wall form part 12

PAGE

Thickness of walls 13

Conditions relating to the wall 16

Construction materials and workmanship 17

Loading on walls 24

End restraint 24

Openings, recesses, overhangs and

chases 26

Lateral support by roofs and floors 27

Interruption of lateral support 30

Small single storey non-residential

buildings and annexes 30

Section 2D: Proportions for masonry

chimneys above the roof surface 34

Height to width relationship 34

Section 2E: Foundations of plain

concrete 35

Conditions relating to the ground 35

Design provisions 35

Minimum width of strip foundations 35

Minimum depth of strip foundations 36

Section 3: Wall Cladding 37

General 37

Technical Approach 37

Loading 37

Fixings 37

Further Guidance 38

Section 4: Roof Covering 39

Materials 39

Recovering of roofs 39

DISPROPORTIONATE COLLAPSE 40

The Requirement 40

Guidance 41

Performance 41

Introduction 41

Section 5: Reducing the sensitivity

of the building to disproportionate

collapse in the event of an accident 42

Alternative Approach 43

Contents

1

A

Approved Document A

PAGE

DIAGRAMS

1. Size and proportion of residential

buildings of not more than 3 storeys 13

2. Size and proportion of non-residential

buildings and annexes 14

3. Determination of wall thickness 15

4. Parapet walls: height 16

5. Maximum floor area enclosed by

structural walls 17

6. Map showing wind speeds in m/s 18

7. Maximum height of buildings 19

8. Measuring storey and wall heights 20

9. Compressive strength of masonry

units 22

10. Declared compressive strength of

masonry units 23

11. Maximum span of floors 24

12. Differences in ground level 25

13. Openings in a buttressing wall 26

14. Buttressing 27

15. Sizes of openings and recesses 28

16. Lateral support by floors 29

17. Lateral support at roof level 30

18. Size and location of openings 31

19. Wall thickness 32

20. Horizontal and lateral restraint at

roof level 33

21. Proportions for masonry chimneys 34

22. Elevation of stepped foundation 35

23. Piers and chimneys 35

24. Foundation dimensions 35

25. Area at risk of collapse in the event

of an accident 44

PAGE

TABLES

1. Areas at risk from House Longhorn

Beetle 11

2. Wall types considered in this section 12

3. Minimum thickness of certain

external walls, compartment walls,

and separating walls 15

4. Imposed loads 17

5. Cavity wall ties 21

6. Compressive Strength of Masonry

Units complying with BS EN 771-1

to 5 21

7. Normalised compressive strength

of masonry unit of clay and calcium

silicate blocks complying with BS

EN 771-1 and 2 24

8. Value of factor ‘x’ 28

9. Lateral support for walls 28

10. Minimum width of strip foundations 36

11. Building Classes 42

Structure Approved Document A

2

A CONTENTS

THE APPROVED DOCUMENTS

This document is one of a series that has been

approved by the First Secretary of State for the

purpose of providing practical guidance with

respect to the requirements of Schedule 1 to

and Regulation 7 of the Building Regulations

2000 (SI 2000/2531) for England and Wales. SI

2000/2531 has been amended by the Building

(Amendment) Regulations 2001 (SI 2001/3335),

by the Building (Amendment) Regulations 2002

(SI 2002/440), by the Building (Amendment)

(No. 2) Regulations 2002 (SI 2002/2871), by the

Building (Amendment) Regulations 2003 (SI

2003/2692) and by the Building (Amendment)

Regulations 2004 (SI 2004/1465).

At the back of this document is a list of all

the documents that have been approved and

issued by the Secretary of State for this

purpose.

Approved Documents are intended to provide

guidance for some of the more common

building situations. However, there may well be

alternative ways of achieving compliance with

the requirements. Thus there is no obligation

to adopt any particular solution contained in

an Approved Document if you prefer to meet

the relevant requirement in some other way.

Other requirements

The guidance contained in an Approved

Document relates only to the particular

requirements of the Regulations which that

document addresses. The building work will

also have to comply with the requirements of

any other relevant paragraphs in Schedule 1 to

the Regulations.

There are Approved Documents which give

guidance on each of the parts of Schedule 1

and on regulation 7.

LIMITATION ON REQUIREMENTS

In accordance with regulation 8, the

requirements in Parts A to K and N of Schedule

1 to the Building Regulations do not require

anything to be done except for the purpose of

securing reasonable standards of health and

safety for persons in or about the buildings.

MATERIALS AND WORKMANSHIP

Any building work which is subject to

requirements imposed by Schedule 1 to the

Building Regulations should, in accordance

with regulation 7, be carried out with proper

materials and in a workmanlike manner.

You may show that you have complied with

regulation 7 in a number of ways. These

include the appropriate use of a product

bearing CE marking in accordance with the

Construction Products Directive (89/106/EEC)1

as amended by the CE Marking Directive

(93/68/EEC)2, or a product complying with an

appropriate technical specification (as defined

in those Directives), a British Standard, or an

alternative national technical specification of

any state which is a contracting party to the

European Economic Area which, in use, is

equivalent, or a product covered by a national

or European certificate issued by a European

Technical Approval Issuing body, and the

conditions of use are in accordance with the

terms of the certificate. You will find further

guidance in the Approved Document

supporting regulation 7 on materials and

workmanship.

Independent certification schemes

There are many UK product certification

schemes. Such schemes certify compliance

with the requirements of a recognised

document which is appropriate to the purpose

for which the material is to be used. Materials

which are not so certified may still conform to

a relevant standard.

Many certification bodies which approve such

schemes are accredited by UKAS.

Technical specifications

Building Regulations are made for specific

purposes; health and safety, energy

conservation and the welfare and convenience

of disabled people. Standards and technical

approvals are relevant guidance to the extent

that they relate to these considerations.

However, they may also address other aspects

of performance such as serviceability, or

aspects which although they relate to health

and safety are not covered by the Regulations.

When an Approved Document makes reference

to a named standard, the relevant version of

the standard is the one listed at the end of the

publication. However, if this version has been

revised or updated by the issuing standards

body, the new version may be used as a source

of guidance provided it continues to address

the relevant requirements of the Regulations.

The appropriate use of a product which

complies with a European Technical Approval

as defined in the Construction Products

Directive will meet the relevant requirements.

Use of Guidance

Approved Document A Structure

3

THE BUILDING REGULATIONS 2000 A

1 As implemented by the Construction Products

Regulations 1991 (S.1. 1991/1620).

2 As implemented by the Construction Products

(Amendment) Regulations 1994 (S. 1. 1994/3051).

The Department intends to issue periodic

amendments to its Approved Documents to

reflect emerging harmonised European

Standards. Where a national standard is to be

replaced by a European harmonised Standard,

there will be a co-existence period during

which either standard may be referred to. At

the end of the co-existence period the national

standard will be withdrawn.

THE WORKPLACE (HEALTH,

SAFETY AND WELFARE)

REGULATIONS 1992

The Workplace (Health, Safety and Welfare)

Regulations 1992 contain some requirements

which affect building design. The main

requirements are now covered by the Building

Regulations, but for further information see:

Workplace health, safety and welfare, The

Workplace (Health, Safety and Welfare)

Regulations 1992, Approved Code of Practice

and Guidance; The Health and Safety

Commission, L24; Published by HMSO 1992;

ISBN 0-11-886333-9.

The Workplace (Health, Safety and Welfare)

Regulations 1992 apply to the common parts of

flats and similar buildings if people such as

cleaners and caretakers are employed to work

in these common parts. Where the

requirements of the Building Regulations that

are covered by this Part do not apply to

dwellings, the provisions may still be required

in the situations described above in order to

satisfy the Workplace Regulations.

OTHER FORMS OF HOUSE

CONSTRUCTION

This Approved Document includes guidance on

structural elements of residential buildings of

traditional masonry construction. It is

recognised, however, that there are other

suitable forms of construction in use in the

housing sector some of which (e.g. timber

framed) have been in common use for a

number of years and have demonstrated an

adequate performance in compliance with the

A1 requirement. Such alternative forms include

prefabricated timber, light steel and pre-cast

concrete framed construction.

A number of guidance documents relating to

these alternative forms are presently being

developed by industry. The intention is to

reference these in this Approved Document as

soon as they become available and are

approved by the Secretary of State.

EUROCODES

The British Standards Institution will shortly be

publishing a series of Structural Eurocodes,

together with their National Annexes. These

Eurocodes are CEN Standards comprising

many Parts which, when used in conjunction

with their National Annexes and when approved

by the Secretary of State, are intended to be

referenced in this Approved Document as

practical guidance on meeting the Part A

Requirements.

Structure Approved Document A

4

A THE BUILDING REGULATIONS 2000

This Approved Document deals with the

following Requirements which are contained in

the Building Regulations 2000 (as amended by

SI 2001/3335, SI 2002/440, SI 2002/2871 and

SI 2003/2692.

The Requirements

Approved Document A Structure

5

LOADING AND GROUND MOVEMENT A1/2

Loading

A1. (1) The building shall be constructed so that the combined dead,

imposed and wind loads are sustained and transmitted by it to the

ground -

(a) safely; and

(b) without causing such deflection or deformation of any part

of the building, or such movement of the ground, as will

impair the stability of any part of another building.

(2) In assessing whether a building complies with sub paragraph (1)

regard shall be had to the imposed and wind loads to which it is likely

to be subjected in the ordinary course of its use for the purpose for

which it is intended.

Ground Movement

A2. The building shall be constructed so that ground movement

caused by :-

(a) swelling, shrinkage or freezing of the subsoil; or

(b) land-slip or subsidence (other than subsidence arising from

shrinkage), in so far as the risk can be reasonably foreseen,

will not impair the stability of any part of the building.

Requirement Limits on application

Introduction

0.1 In the Secretary of State’s view the

requirements of A1 and A2 will be met by

following the recommendations given in the

documents listed in Section 1 or by adopting

the guidance in Sections 2-4

a. Section 1 is relevant to all building types

and lists Codes, Standards and other

references for structural design and

construction but, where they do not give

precise guidance, consideration should be

given to paragraph 0.2.

b. Section 2 give sizes of structural

elements for certain residential buildings and

other small buildings of traditional

construction.

c. Section 3 gives guidance on the support

and fixing of wall cladding

d. Section 4 gives guidance where roofs are

to be re-covered as a material alteration as

defined in the Regulations.

0.2 The safety of a structure depends on the

successful combination of design and

completed construction, particularly :

a. The design should be based on

identification of the hazards to which the

structure is likely to be subjected and

assessment of the risks. The selection of

relevant critical situations for design should be

made reflecting the conditions that can

reasonably be foreseen during future use.

b. Loading. Dead load, imposed load and

wind load should be in accordance with the

current Codes of Practice referred to in Section

1 of this document.

c. Properties of materials

d. Detailed design and assembly of the

structure

e. Safety factors

f. Workmanship

The numeric values of safety factors, whether

expressed explicitly or implicitly in design

equations, or design values, should be derived

from considerations of the above aspects of

design and construction as a whole. A change

in any one of these aspects may disturb the

safety of structure.

Loads used in calculations should allow for

possible dynamic, concentrated and peak load

effects that may occur.

0.3 Grandstands and structures erected in

places of public assembly may need to sustain

the synchronous or rhythmic movement of

numbers of people. It is important to ensure

that the design of the structure takes these

factors into account so as to avoid the

structure being impaired or causing alarm to

people using the structure.

Interim guidance on the design of grandstands

may be found in “Dynamic performance

requirements for permanent grandstands

subject to crowd action, Interim Guidance on

assessment and design” published by the

Institution of Structural Engineers, November

2001.

Supplementary advice on the dynamic testing

of grandstands and seating decking has been

published in an Advisory Note by the Institution

of Structural Engineers June 2002.

Guidance

Structure Approved Document A

6

A1/2 LOADING AND GROUND MOVEMENT

Introduction

1.1 This section is relevant to all building types

and lists codes, standards and other references

for structural design and construction.

References

1.2 Loading:

a. Dead and imposed loads

BS 6399 : Loading for buildings :

Part 1 : 1996 Code of practice for dead and

imposed loads.

b. Wind Loads

BS 6399 : Loading for buildings:

Part 2 : 1997 Code of practice for wind loads

BRE Digest 436 : Parts 1, 2 and 3 (Brief

guidance for using BS 6399 : Part 2).

c. Imposed roof loads

BS 6399 : Loading for buildings:

Part 3 : 1988 Code of practice for imposed roof

loads.

1.3 Structural work of timber:

BS 5268 : Structural use of timber :

Part 2 : 2002 Code of practice for permissible

stress design, materials and workmanship.

Part 3 : 1998 Code of practice for trussed

rafter roofs.

BS 8103 : Structural design of low-rise

buildings.

Part 3 : 1996 Code of practice for timber floors

and roofs for housing.

1.4 Structural work of masonry:

BS 5628 : Code of practice for use of masonry:

Part 1 : 1992 Structural use of unreinforced

masonry.

Part 2 : 2000 Structural use of reinforced and

prestressed masonry.

Part 3 : 2001 Materials and components,

design and workmanship.

BS 8103 : Structural design of low-rise

buildings:

Part 1 : 1995 Code of practice for stability, site

investigation, foundations and ground floor

slabs for housing.

Part 2 : 1996 Code of practice for masonry

walls for housing.

1.5 Structural work of reinforced, prestressed

or plain concrete:

BS 8110 : Structural use of concrete:

Part 1 : 1997 Code of practice for design and

construction.

Part 2 : 1985 Code of practice for special

circumstances.

Part 3 : 1995 Design charts for singly

reinforced beams, doubly reinforced beams and

rectangular columns.

BS 8103 : Structural design of low rise

buildings: Part 4 : 1995 Code of practice for

suspended concrete floors for housing.

1.6 Structural work of steel:

BS 5950 : Structural use of steelwork in

Building:

Part 1 : 2000 Code of practice for design in

simple and continuous construction : hot rolled

and welded sections.

Part 2 : 2001 Specification for materials,

fabrication and erection, hot rolled sections.

Part 3 : Design in composite construction :

Section 3.1 : 1990 Code of practice for design

of simple and continuous composite beams.

Part 4 : 1994 Code of practice for design of

composite slabs with profiled steel sheeting.

Part 5 : 1998 Code of practice for design of

cold formed thin gauge sections.

BRE Digest 437 - Industrial platform floors :

mezzanine and raised storage.

1.7 Structural work of aluminium:

BS 8118 : Structural use of aluminium:

Part 1 : 1991 Code of practice for design.

Part 2 : 1991 Specification for materials,

workmanship and protection.

1.8 Foundations:

BS 8002 : 1994 Code of practice for earth

retaining structures.

BS 8004 : 1986 Code of practice for

foundations.

Section 1: Codes, Standards and

References for all Building types

Approved Document A Structure

7

CODES, STANDARDS AND REFERENCES A1/2

Ground Movement (Requirement

A2b.)

1.9 There may be known or recorded

conditions of ground instability, such as that

arising from landslides, disused mines or

unstable strata which, if ignored, can have a

devastating effect on the safety of a building

and its environs. Such conditions should be

taken into account in the design of the building

and its foundations. Attention is drawn to DOE

Planning Policy Guidance Note 14

Development on unstable land (obtainable from

the Stationary office), which sets out the broad

planning and technical issues relating to

development on unstable land.

The Department has also sponsored a series of

reviews aimed at determining the scale and

nature of problems arising from mining

instability, natural underground cavities and

adverse foundation conditions. Databases of

both subsidence incidents and subsidence

potential produced from these reviews are

available from the following licence holders :

British Geological Survey, Sir Kingsley Dunham

Centre, Keyworth, Nottingham NG12 5GG.

Landmark, 7 Abbey Court, Eagle Way, Exeter,

Devon EX2 7HY,

Peter Brett Associates, 16 Westcote Road,

Reading, Berkshire RG20 2DE.

Catalytic Data Ltd., The Spinney, 19 Woodlands

Road, Bickley, Kent BRI 2AD

The reports from these reviews, which include

1:250,000 scale maps showing the distribution

of the physical constraints, are available from

the following organisations :

Arup Geotechnics, 1991. Review of mining

instability in Great Britain.

Obtainable from Arup Geotechnics, Bede

House, All Saints, Newcastle-upon-Tyne NE1

2EB.

Applied Geology Ltd., 1994. Review of

instability due to natural underground cavities

in Great Britain.

Obtainable from Kennedy & Donkin Ltd., 14

Calthorpe Road, Edgbaston, Birmingham Bl5

1TH.

Wimpey Environmental Ltd., and National

House Building Council, 1995. Foundation

conditions in Great Britain, a guide for planners

and developers. Obtainable from ESNR

International Ltd., 16 Frogmore Road, Hemel

Hempstead, Hertfordshire HP3 9RW.

Existing buildings

1.10 Compliance with Part A (Structure) is

required in certain classes of change of use of

a building, subject to the control of Regulations

5 and 6. Guidance relevant to structural

appraisals related to ‘change of use’ is given in

the following documents :

a. BRE Digest 366 : Structural Appraisal of

Existing Buildings for Change of Use.

b. The Institution of Structural Engineers

Report Appraisal of Existing Structures, 1996.

Note: With reference to the item ‘design

checks’ in the above mentioned Institution of

Structural Engineers report the choice of

various partial factors should be made to suit

the individual circumstances of each case.

Structure Approved Document A

8

A1/2 CODES, STANDARDS AND REFERENCES

General

2.1 This Section is presented as follows:

Section 2A

Basic requirements for stability.

Section 2B

Sizes of certain timber members in floors and

roofs for dwellings.

Areas at risk from house longhorn beetle.

Section 2C

Thickness of masonry walls in certain

residential buildings of not more than 3 storeys,

small single storey non-residential buildings

and annexes.

Section 2D

Proportions for masonry chimneys.

Section 2E

Foundations of plain concrete.

2.2 Section 2A gives general rules which must

be observed in following Sections 2B and 2C.

Sections 2B to 2E may be used independently

of each other.

Throughout this section the diagrams are only

illustrative and do not show all the details of

construction.

Definitions

2.3 The following meanings apply to terms

throughout this Section:

Buttressing wall A wall designed and

constructed to afford lateral support to another

wall perpendicular to it, support being provided

from the base to the top of the wall.

Cavity width The horizontal distance between

the two leaves of a cavity wall.

Compartment wall A wall constructed as a

compartment wall to meet the requirements of

regulation B3(2).

Dead load The load due to the weight of all

walls, permanent partitions, floors, roofs and

finishes including services, and all other

permanent construction.

Imposed load The load assumed to be

produced by the intended occupancy or use,

including the weight of movable partitions,

distributed, concentrated, impact, inertia and

snow loads, but excluding wind loads.

Pier A member which forms an integral part of

a wall, in the form of a thickened section at

intervals along the wall, so as to afford lateral

support to the wall to which it is bonded or

securely tied.

Separating wall A wall or part of a wall which

is common to adjoining buildings, and

constructed to meet the requirements of

regulation B3(2).

Spacing The distance between the longitudinal

centres of any two adjacent timber members of

the same type, measured in the plane of floor,

ceiling or roof structure.

Span The distance measured along the centre

line of a member between the centres of any

two adjacent bearings or supports.

Supported Wall A wall to which lateral support

is afforded by a combination of buttressing

walls piers or chimneys acting in conjunction

with floor(s) or roof.

Wind load The load due to the effect of wind

pressure or suction.

Section 2: Sizes of Structural Elements for

certain residential buildings and other small

buildings of Traditional Construction

Approved Document A Structure

9

SIZES OF STRUCTURAL ELEMENTS A1/2

2A1 This section must be used in conjunction

with sections 2B and 2C and its principles

relate to all forms of low rise residential

buildings.

2A2 Adequate provision shall be made to

ensure that the building is stable under the

likely imposed and wind loading conditions.

This will commonly necessitate meeting the

following requirements:

a. That the overall size and proportioning of

the building are limited in accordance with the

specific guidance for each form of

construction.

b. That a suitable layout of walls (both

internal and external) forming a robust 3

dimensional box structure in plan is

constructed with restriction on the maximum

size of cells measured in accordance with the

specific guidance for each form of

construction.

c. That the internal and external walls are

adequately connected by either masonry

bonding or by using mechanical connections.

d. That the intermediate floors and roof are

of such construction and interconnection with

the walls that they provide local support to the

walls and also act as horizontal diaphragms

capable of transferring the wind forces to

buttressing elements of the building.

Note: A traditional cut timber roof (i.e. using

rafters, purlins and ceiling joists) generally has

sufficient built in resistance to instability and

wind forces (eg from either hipped ends, tiling

battens, rigid sarking, or the like). However, the

need for diagonal rafter bracing equivalent to

that recommended in BS 5268: Part 3: 1998 or

Annex H of BS 8103: Part 3: 1996 for trussed

rafter roofs, should be considered especially

for single-hipped and non-hipped roofs of

greater than 40° pitch to detached houses.

Section 2A: Basic Requirements for Stability

Structure Approved Document A

10

A1/2 SIZES OF STRUCTURAL ELEMENTS

Sizing of Members

2B1 Guidance on the sizing of certain

members in floors and roofs is given in “Span

tables for solid timber members in floors,

ceilings and roofs (excluding trussed rafter

roofs) for dwellings”, published by TRADA,

available from Chiltern House, Stocking Lane,

Hughenden Valley, High Wycombe, HP14 4ND,

Bucks.

Alternative guidance is available in BS 5268:

Part 2: 2002 Code of Practice for permissible

stress design, materials and workmanship, BS

5268: Part 3: 1998, Code of Practice for

trussed rafter roofs and BS 8103: Part 3:

Structural design of low-rise buildings, Code of

Practice for timber floors and roofs for

dwellings.

House Longhorn Beetle

2B2 In the geographical areas specified in

Table 1, softwood timber for roof construction

or fixed in the roof space, including ceiling

joists within the void spaces of the roof, should

be adequately treated to prevent infestation by

the House Longhorn Beetle (Hylotrupes bajulus

L).

Guidance on suitable preservative treatments is

given within the British Wood Preserving and

Damp-Proofing Associations Manual (2000

revision), available from 1 Gleneagles House,

Vernongate, South Street, Derby DE1 1UP.

Section 2B: Sizes of certain timber

members in floors and roofs for dwellings.

Areas at risk from House Longhorn Beetle

Approved Document A Structure

11

SIZES OF STRUCTURAL ELEMENTS A1/2

Geographical Area

In the Borough of Bracknell Forest the parishes of Sandhurst and Crowthorne.

The Borough of Elmbridge

In the District of Hart, the parishes of Hawley and Yateley

The District of Runnymede

The Borough of Spelthorne

The Borough of Surrey Heath

In the Borough of Rushmoor, the area of the former district of Farnborough The Borough of Woking

Table 1 Areas at risk from House Longhorn Beetle

Application

2C1 This Section applies to the following

building types:

a. residential buildings of not more than

three storeys, and

b. small single storey non-residential

buildings, and

c. small buildings forming annexes to

residential buildings. (including garages and

outbuildings).

Wall types

2C2 Only the types of wall given in Table 2,

which must extend to the full storey height, and

parapet walls are considered in this section.

The use of this Section

2C3 When using this Section it should be

noted that:

a. this section must be used in conjunction

with Section 2A;

b. if wall thickness is to be determined

according to paragraphs 2C5 to 2C13, all

appropriate design conditions given in this

section must be satisfied;

c. walls should comply with the relevant

requirements of BS 5628: Part 3:2001, except

as regards the conditions given in paragraphs

2C4 and 2C14 to 2C38.

d. in formulating the guidance of this

section the worst combination of

circumstances likely to arise was taken into

account. If a requirement of this part is

considered too onerous in a particular case it

may be appropriate to consider a minor

departure on the basis of judgement and

experience, or to show adequacy by

calculation in respect of the aspect of the wall

which is subject to the departure rather than

for the entire wall;

e. the guidance given is based upon the

compressive strengths of bricks and blocks

being not less than indicated in Tables 6 and 7.

BS 5628 Part 1: 1992 gives design strengths

for walls where the suitability for use of

masonry units of other compressive strengths

is being considered.

Conditions relating to the

building of which the wall

forms part

2C4 This Section applies only to buildings

having proportions within the following

parameters (see Diagrams 1 and 2)

a. residential buildings of not more than 3

storeys:

i. the maximum height of the building

measured from the lowest finished

ground level adjoining the building to the

highest point of any wall or roof should

not be greater than 15m, subject to the

limits of paragraph 2C16,

ii. the height of the building H should not

exceed twice the least width of the

building W1,

iii. the height of the wing H2 should not

exceed twice the least width of the wing

W2 where the projection P exceeds twice

the width W2.

b. small single-storey non-residential

buildings: height H should not exceed 3m and

W (being the greatest length or width of the

building) should not exceed 9m (see Diagram

2), subject to the limits of paragraph 2C16.

Section 2C: Thickness of walls in certain

small buildings

Structure Approved Document A

12

A1/2 SIZES OF STRUCTURAL ELEMENTS

Residential buildings of up to three storeys

external walls

internal load bearing walls

compartment walls

separating walls

Small single storey non-residential buildings and annexes

external walls

internal load bearing walls

Table 2 Wall types considered in this Section

c. annexes: height H as variously indicated

in Diagram 2 should not exceed 3m, subject to

the limits of paragraph 2C16.

Thickness of walls

2C5 General wall thickness may be determined

according to this Section provided:

a. condition relating to the building of which

the wall forms part (see paragraphs 2C4, 2C14

to 2C16, 2C38) and

b. condition relating to the wall (see

paragraphs 2C17 to 2C37) are met. (See

diagram 3)

2C6 Solid external walls, compartment walls

and separating walls in coursed brickwork

or blockwork: Solid walls constructed of

coursed brickwork or blockwork should be at

least as thick as 1/16 of the storey height.

Further requirements are given in Table 3.

2C7 Solid external walls, compartment walls

and separating walls in uncoursed stone,

flints etc.: The thickness of walls constructed

in uncoursed stone, flints, clunches, of bricks

or other burnt or vitrified material should not be

less than 1.33 times the thickness determine

by paragraph 2C6.

2C8 Cavity walls in coursed brickwork or

blockwork: All cavity walls should have leaves

at least 90mm thick and cavities at least 50mm

wide. The wall ties should have a horizontal

spacing of 900mm and a vertical spacing of

450mm, which is equivalent to 2.5 ties per

square metre. Wall ties should also be

provided, spaced not more than 300mm apart

vertically, within a distance of 225mm from the

vertical edges of all openings, movement joints

and roof verges. For selection of wall ties for

use in a range of cavity widths refer to Table 5.

For specification of cavity wall ties refer to

paragraph 2C19.

For external walls, compartment walls and

separating walls in cavity construction, the

combined thickness of the two leaves plus

10mm should not be less than the thickness

determined by paragraph 2C6 and Table 3 for a

solid wall of the same height and length.

2C9 Walls providing vertical support to

other walls: Irrespective of the material used in

the construction, a wall should not be less in

thickness than any part of the wall to which it

gives vertical support.

2C10 Internal loadbearing walls in

brickwork or blockwork: (except compartment

walls or separating walls) should have a

thickness not less than:

(specified thickness from Table 3)

-5mm

2

Approved Document A Structure

13

SIZES OF STRUCTURAL ELEMENTS A1/2

if P is more than 2W2

then W2 to be not less than 0.5 H2

See para 2C4

W1 to be not less than 0.5 H

Maximum height Minimum height

H

not to

exceed

15m

lowest

ground level

W1 W1

W1 W2

H2

H H

P

Diagram 1 Size and proportion of residential buildings of not more than 3 storeys

Continued on page 16

Structure Approved Document A

14

A1/2 SIZES OF STRUCTURAL ELEMENTS

II

II

II

II

II

II

a. Non-Residentail Buildings

b. Annexes

See para 2C4b and 2C4c

Flat roof buildings

Flat roof annexes

annexe

PItched roof annexes

(type 1)

PItched roof annexes

(type 2)

annexe

annexe

Pitched roof buildings

Maximum roof

slope 40˚

Maximum roof

slope 40˚

Residential

building

Residential

building

H

3.0 m

max.

H

3.0 m

max.

H

H

H

H

3.5 m

max.

3.0 m

max.

4.5 m

max.

3.0 m

max.

H

3.6 m

max.

Note

Height H should be measured

from top of the foundation or

from the underside of the floor

slab where this provides effective

lateral restraint.

3.5 m

max.

3.5 m

max.

3.0 m

max.

Maximum roof

slope 40˚

Diagram 2 Size and proportion of non-residential buildings and annexes

Approved Document A Structure

15

SIZES OF STRUCTURAL ELEMENTS A1/2

YES

YES

NO

NO

See para 2C5

Conditions – building

(a) limitations on size and proportion of building and

parts of the building (paragraph 2C4 and 2C38)

(b) maximum allowable floor areas (paragraph 2C14)

(c) maximum imposed and wind loads

(paragraphs 2C15 and 2C16)

Conditions – wall

(a) maximum allowable length and height of wall

(paragraphs 2C17–2C18)

(b) construction materials and workmanship

(paragraphs 2C19–2C22)

(c) loading on walls (paragraph 2C23–2C24)

(d) end restraints (paragraphs 2C25–2C27)

(e) openings, recesses, overhangs and chases

(paragraphs 2C28–2C31)

(f) lateral support by roofs and floors

(paragraphs 2C32–2C37)

(g) conditions relating to external walls of small

single storey non-residential buildings and

annexes (paragraphs 2C38)

Conditions relating

to the building of

which the wall

forms part

Conditions relating

to the wall

Are

condtions

relating to

the wall

satisfied?

Wall thickness

given in paragraphs

2C6 to 2C13

may be used

Outside scope

of this part

Outside scope

of this part

Are

condtions

relating to

the building

satisfied?

Diagram 3 Determination of wall thickness

Height of wall Length of wall Minimum thickness of wall

not exceeding 3.5m not exceeding 12m 190mm for whole of its height

exceeding 3.5m but not exceeding 9m not exceeding 9m 190mm for whole of its height

exceeding 9m 290mm from the based for the height of

one storey and 190mm for the rest of its height

exceeding 9m but not exceeding 12m not exceeding 9m 290mm from the based for the height of

one storey and 190mm for the rest of its height

exceeding 9m 290mm from the base for the height of

but not exceeding 12m two storeys and 190mm for the rest of its height

Table 3 Minimum thickness of certain external walls, compartment walls and

separating walls

except for a wall in the lowest storey of a three

storey building, carrying load from both upper

storeys, which should have a thickness as

determined by the equation or 140mm

whichever is the greatest.

2C11 Parapet walls: The minimum thickness

and maximum height of parapet walls should

be as given in Diagram 4.

2C12 Single leaves of certain external walls:

The single leaf of external walls of small single

storey non-residential buildings and of annexes

need be only 90mm thick, notwithstanding

paragraphs 2C38

2C13 Modular bricks and blocks: Where walls

are constructed of bricks or blocks having

modular dimensions derived from BS6649 -

1985, wall thicknesses prescribed in this

section which derive from a dimension of brick

or block may be reduced by an amount not

exceeding the deviation from work size

permitted by a British Standard relating to

equivalent sized bricks or blocks made of the

same material.

2C14 Maximum floor area: The guidance of

this Section assumes that no floor enclosed by

structural walls on all sides exceeds 70m2; and

that no floor without a structural wall on one

side exceeds 36m2. (See Diagram 5)

2C15 Imposed loads on roofs, floors and

ceilings: The design considerations given in

this Section are intended to be adequate for

the imposed loads given in Table 4.

2C16 Maximum height of buildings: The design

guidance in this section is based on BS 6399 :

Part 2 : 1997. The maximum heights of

buildings given in Table c of Diagram 7

correlate to various site exposure conditions

and wind speeds. A map showing wind speeds

is given in Figure 1 of Diagram 6.

Conditions relating to the wall

2C17 Maximum allowable length and height

of the wall: This Section does not deal with

walls longer than 12m, measured from centre

to centre of buttressing walls, piers or

chimneys providing restraint, or with walls

exceeding 12m in height. (see also Table 3).

Structure Approved Document A

16

A1/2 SIZES OF STRUCTURAL ELEMENTS

level of junction

of wall and

structural roof

Type A

Cavity

wall

Note: t should be less than or equal to T

See para 2C11

Hp

t1

t

T

t2

level of junction

of wall and

structural roof

Type B

Cavity

wall

Hp

t

T

Wall

type

Thickness

(mm)

Parapet height Hp

to be not more than

(mm)

t1 +t2

equal or less than 200 600

t = 150 600

t1 +t2

greater than 200

equal or less than 250 860

t = 190 760

t = 215 860

Diagram 4 Parapet walls: height

2C18 Rules of measurement for heights of

walls and storeys: The height of a wall or a

storey should be measured in accordance with

the rules in Diagram 8.

Construction materials and

workmanship

2C19 Wall ties: Wall ties should either comply

with BS 1243, DD 140, or BS EN 845-1 and

should be material references 1 or 3 in BS EN

845 Table A 1 austenitic stainless steel. Wall

ties should be selected in accordance with

Table 5 of this A. D.

2C20 Masonry Units: Walls should be properly

bonded and solidly put together with mortar and

constructed of masonry units conforming to:-

a. clay bricks or blocks conforming to BS

3921: 1985 or BS 6649: 1985 or BS EN 771-1

b. calcium silicate bricks conforming to BS

187: 1978 or BS 6649: 1985 or BS EN 771-2

c. concrete bricks or blocks conforming to

BS 6073: Part 1: 1981 or BS EN 771-3 or 4

d square dressed natural stone conforming

to the appropriate requirements described in

BS EN 771-6 or BS 5628: Part 3: 2001

e. Manufactured stone complying with BS

6457: 1984 and BS EN 771-5

2C21 Compressive strength of masonry

units: Minimum compressive strength

requirements for masonry units according to

BS Standards and BS EN Standards are given

in Diagrams 9 and 10 respectively.

With reference to Diagram 9, the compressive

strengths given for bricks and blocks are those

values in accordance with the appropriate

British Standards ie. BS 3921, BS 6073-1, BS

187, BS 5390 and BS 6649.

With reference to Diagram 10, the masonry

units indicated for Conditions A, B and C

should have declared compressive strengths of

not less than the values given in Table 6.

Normalised compressive strengths for block

sized clay and calcium silicate masonry units

not complying with brick dimensional format

are given in Table 7.

Approved Document A Structure

17

SIZES OF STRUCTURAL ELEMENTS A1/2

Area not

exceeding 70m2.

Area not

exceeding 70m2.

Area not

exceeding 70m2.

Area not

exceeding

36m2.

Area not

exceeding

36m2.

Area not

exceeding

36m2.

Area not

exceeding

36m2.

a. Structural walls on all sides b. Structural walls on three sides

See para 2C14

Diagram 5 Maximum floor area enclosed by structural walls

Element Loading

distributed loads

roof 1.00 kN/m2 for spans not exceeding 12m

1.5 kN/m2 for spans not exceeding 6m

floors distrubted load: 2.00kN/m2

ceilings distributed load: 0.25kN/m2

together with concentrated load: 0.9kN

Table 4 Imposed Loads

Continued on page 24

Structure Approved Document A

18

A1/2 SIZES OF STRUCTURAL ELEMENTS

Figure 2 Topographic zones for Factor T

See para 2C16

zone 2

0.25Lu

zone 1

0.25Lu 0.4Lu

zone 2

0.4Lu

zone 3

1.2Lu

Lu

Cliffs and

Escarpments

Wind direction

zone 2

0.4Lu

zone 1

0.4Lu 0.4Ld

zone 2

0.4Ld

Lu Ld

Wind direction

Hills and Ridges

Lu – is slope on upwind side

Ld – is slope on downwind side

Figure 1 Map of wind speeds in m/s

24

24

25

25

23

23

24

23

22

20

21

24

Newcastle

Carlisle

Preston Leeds

York

Liverpool Manchester

Sheffield

Stoke

Nottingham

Leicester

Birmingham

Aberystwyth Northampton

Bedford

Norwich

Kingstonupon-

Hull

Ipswich

Oxford

LONDON

Bournemouth Brighton

Bristol

Cardiff

Plymouth

Swansea

Diagram 6 Map showing wind speeds in m/s for maximum height of buildings

Approved Document A Structure

19

SIZES OF STRUCTURAL ELEMENTS A1/2

Diagram 7 Maximum height of buildings

See para 2C16

Road map

wind spread V

from Figure 1

diagram 6

Find the topographic

zone for the

site from Figure 2

diagram 6 and obtain

factor from Table a

Obtain value of

factor A

from Table b

Calculate

value of factor S

from:

S = V x T x A

Obtain maximum

allowable building

height from

Table c

Table b Factor A

Topographic category and average slope of whole Factor T

hillside, ridge, cliff or escarpment Zone 1 Zone 2 Zone 3

Category 1 : Nominally flat terrain, average slope < 1/20 1.0 1.0 1.0

Category 2 : Moderately steep terrain, average slope < 1/5 1.24 1.13 1.10

Category 3 : Steep terrain, average slope > 1/5 1.36 1.20 1.15

Table b Factor A

Site Altitude (m) Factor A

0 1.00

50 1.05

100 1.10

150 1.15

200 1.20

300 1.30

400 1.40

Table c Maximum allowable building height (m)

Factor Country Sites Town Sites*

S Distance to the coast Distance to the coast

< 10km 10–50km > 50km < 10km 10–50km > 50km

24 15 15 15 15 15 15

25 11.5 14.5 15 15 15 15

26 8 10.5 13 15 15 15

27 6 8.5 10 15 15 15

28 4.5 6.5 8 13.5 15 15

29 3.5 5 6 11 13 14.5

30 3 4 5 9 11 12.5

31 3.5 4 8 9.5 10.5

32 3 3.5 7 8.5 9.5

33 3 6 7.5 8.5

34 5 7 8

35 4 6 7

36 3 5.5 6

37 4.5 5.5

38 4 5

39 3 4

40 3

Note: Outside these zones factor T = 10

* For sites on the outskirts of towns not sheltered by other buildings use the values for Country sites

Structure Approved Document A

20

A1/2 SIZES OF STRUCTURAL ELEMENTS

See para 2C18

Top of foundation

Ground level

2.7m max.

H1 H2 H3

Hp II

II

II

D

C

B

A

Base of wall

(see note)

A1

B1

II

2.7m max.

2.7m max.

Line of base

of gable.

2.7m max.

Line of lateral

support to gable

wall along roof

slope.

Line of top

of gable.

Top of wall

or base of

parapet

Line of lateral

support to gable

at ceiling level.

Underside of

roof joist

Key

(a) Measuring Storey Heights

A1 is the ground storey height if the ground floor provides

effective lateral support to the wall i.e. is adequately tied to

the wall or is a suspended floor bearing on the wall.

A is the ground storey height if the ground floor does not

provide effective lateral support to the wall.

Note: If the wall is supported adequately and permanently

on both sides by suitable compact material, the base of the

wall for the purposes of the storey height may be taken as

the lower level of this support. (Not greater than 3.7m

ground storey height.)

B is the intermediate storey height.

B1 is the top storey height for wall which do not include a

gable.

C is the top storey height where lateral support is given to

the gable at both ceiling level and along the roof slope.

D is the topstorey height for the external walls which include

a gable where lateral support is given to the gable only

along the roof slope.

(b) Measuring Wall Heights

H1 is the height of an external wall that does not include a

gable.

H2 is the height of an internal or separating wall which is

built up to the underside of the roof.

H3 is the height of an external wall which includes a gable.

Hp is the height of a parapet (see Diagram 4). If Hp is

more than 1.2m add to Hp to H1.

Diagram 8 Measuring storey and wall heights

Approved Document A Structure

21

SIZES OF STRUCTURAL ELEMENTS A1/2

Normal cavity

Permissible type of tie

width mm Tie length mm Tie Shape in accordance BS EN 845-1 tie

(Note 1) (Note 2) with BS 1243* (Note 4)

50 to 75 200 Butterfly, double triangle or vertical twist Types 1, 2, 3 or 4 to DD 140-2* and

76 to 90 225 Double triangle or vertical twist

selected on the basis of the design

91 to 100 225 Double triangle (Note 3) or vertical twist

loading and design cavity width.

101 to 125 250 Vertical twist

126 to 150 275 Vertical twist *Although BS1243 and DD 140-2 are due to be

151 to 175 300 Vertical twist withdrawn on 1 February 2005, the tie user classes

(types) given in Tables 1 and 3 of the latter

176 to 300 (See Note 2) Vertical twist style document can continue to be used after this date.

Notes

1 Where face insulated blocks are used the cavity width should be measured from the face of the masonry unit.

2 The embedment depth of the tie should not be less than 50mm in both leaves. For cavities wider than 180mm calculate the

length as the structural cavity width plus 125mm and select the nearest stock length.

3 Double triangle ties of this shape having a strength to satisfy Type 2 of DD 140-2*, are manufactured. Specialist tie manufacturers

should be consulted if 225mm long double triangle format ties are needed for 91 to 100mm cavities.

4 Where BS EN 845-1 ties are used reference needs to be additionally made to DD 140-2* for the selection of the type (ie. types 1,

2, 3 or 4) relevant to the performance levels given in DD140-2.

Table 5 Cavity wall ties

Masonry Clay masonry units to Calcium Silicate masonry Aggregate Autoclaved Manufactured

Unit BS EN 771-1 units to BS EN 771-2 Concrete aerated conc. Stone

Masonry Masonry Masonry

Units to units to units to

BS EN 771-3 BS EN 771-4 BS EN 771-5

Condition A (See diagram 10)

Brick Group 1 Group 2 Group 1 Group 2 6.0 –

6.0 9.0 6.0 9.0

Block See Table 7 See Table 7 See Table 7 See Table 7 3.1* 3.1

Condition B (See diagram 10)

Brick Group 1 Group 2 Group 1 Group 2 9.0 –

9.0 13.0 9.0 13.0

Block See Table 7 See Table 7 See Table 7 See Table 7 7.7* 7.7

Condition C (See diagram 10)

Brick Group 1 Group 2 Group 1 Group 2 18.0 –

18.0 25.0 18.0 25.0

Block See Table 7 See Table 7 See Table 7 See Table 7 7.7* 7.7

*These values are dry ground strengths to BS EN 772-1

Notes

1. This table applies to Group 1 and Group 2 units.

2. For the EN 771 series of standards for masonry units the values of declared compressive strengths (N/mm2) given in Table 6 are

mean values.

3. Brick: a masonry unit having work sizes not exceeding 337.5 mm in length or 112.5 mm in height.

4. Block: a masonry unit exceeding either of the limiting work sizes of a brick and with a minimum bed height of 190mm. For blocks

with smaller bed heights, excluding cuts or make up units, the strength requirements are as for brick except for solid external

walls where the blocks should have a compressive strength at least equal to that shown for block for an inner leaf of a cavity wall

in the same position.

5. Group 1 masonry units have not more than 25% formed voids (20% for frogged bricks). Group 2 masonry units have formed

voids greater than 25%, but not more than 55%.

Table 6 Declared Compressive Strength of Masonry Units complying with

BS EN 771 - 1 to 5 (N/mm2)

Any unit complying with BS EN 771-5 will

be acceptable for conditions A, B and C

Structure Approved Document A

22

A1/2 SIZES OF STRUCTURAL ELEMENTS

Hs

Hs

Hs

Hs

Hf

Hs

a. One Storey

b. Two Storeys c. Three Storeys

Underside

of

structural

roof

Underside

of

structural

roof

Underside

of

structural

roof

Topside of

structural floor

Topside of

structural floor

This wall to be at

least 140mm thick

in blockwork or

215mm thick in

brickwork below ground

floor level if height

Hf exceeds 1m.

See para 2C21

Key

Brick 5N/mm2

Block 2.8N/mm2

Brick 15N/mm2

Block 7N/mm2

Where

Hf Less than or equal to 1m – Brick 5N/mm2

Hf Less than or equal to 1m – Block 2.8N/mm2

Where

Hf Greater than 1m – Brick 7N/mm2

Hf Greater than 1m – Block 7N/mm2

Brick 7N/mm2

Block 7N/mm2

Cavity

wall

Internal

wall

Underside

of

structural

roof

Underside

of

structural

roof

Underside

of

structural

roof

Topside of

structural floor

Cavity

wall

Internal

wall

This wall to

be at least

140mm thick

blockwork or

215mm thick

brickwork.

Hs

Diagram 9 Compressive strength of masonry units

Notes

1 If Hs is not greater than 2.7m, the

compressive strength of bricks or blocks

should be used in walls as indicated by the

key.

2 If Hs is greater than 2.7m, the

compressive strength of bricks or blocks

used in the wall shall either be at least

7N/sq mm or as indicated by the key,

whichever is the greater.

3 If the external wall is solid

construction the masonry units should have

a compressive strength of at least that

shown for the internal leaf of a cavity wall in

the same position.

4 The guidance given in the diagram for

walls of two and three storey buildings

should only be used to determine the

compressive strength of the masonry units

where the roof construction is of timber.

Approved Document A Structure

23

SIZES OF STRUCTURAL ELEMENTS A1/2

Hs

Hs

Hs

Hs

Hf

Hs

a. One Storey

b. Two Storeys c. Three Storeys

Underside

of

structural

roof

Underside

of

structural

roof

Underside

of

structural

roof

Topside of

structural floor

Topside of

structural floor

This wall to be at

least 140mm thick

in blockwork or

215mm thick in

brickwork below ground

floor level if height

Hf exceeds 1m.

See para 2C21

Key

Condition A

Condition C

Where

Hf Less than or equal to 1m, Condition A

Where

Hf Greater than 1m, Condition B

Condition B

Cavity

wall

Internal

wall

Underside

of

structural

roof

Underside

of

structural

roof

Underside

of

structural

roof

Topside of

structural floor

Cavity

wall

Internal

wall

This wall to

be at least

140mm thick

blockwork or

215mm thick

brickwork.

Hs

Diagram 10 Declared compressive strength of masonry units

Notes

1 If Hs is not greater than 2.7m, the

compressive strength of bricks or blocks

should be used in walls as indicated by the

key.

2 If Hs is greater than 2.7m, the

compressive strength of bricks or blocks

used in the wall should be at least Condition

B, or as indicated by the key, whichever is

the greater.

3 If the external wall is solid

construction, the masonry units should have

a compressive strength of at least that

shown for the internal leaf of a cavity wall in

the same position.

4 The guidance given in the diagram for

walls of two and three storey buildings

should only be used to determine the

compressive strength of the masonry units

where the roof construction is of timber.

2C22 Mortar: Mortar should be:

a.

i. Mortar designation (iii) according to BS

5628:Part 3:2001

ii. Strength class M4 according to BS EN

998 - 2

iii 1:1: 5 or 6 CEM 1, lime and fine

aggregate measured by volume of dry

materials, or

b. of equivalent or greater strength and

durability to the specification in a. above.

Loading on walls

2C23 Maximum span of floors: The maximum

span for any floor supported by a wall is 6m

where the span is measured centre to centre of

bearing. (see Diagram 11)

2C24 Other loading conditions:

a. Vertical loading on walls should be

distributed. This may be assumed for concrete

floor slabs, precast concrete floors, and timber

floors designed in accordance with Section 2B,

and where the bearing length for lintels is

150mm or greater. Where a lintel has a clear

span of 1200mm or less the bearing length may

be reduced to 100mm.

b. differences in level of ground or other

solid construction between one side of the wall

and the other should be less than 4 times the

thickness of the wall as shown in Diagram 12.

c. the combined dead and imposed load

should not exceed 70kN/m at base of wall. (see

Diagram 12)

d. walls should not be subjected to lateral

load other than from wind, and that covered by

paragraph 2C24(b).

End restraint

2C25 Vertical Lateral Restraint to Walls

The ends of every wall should be bonded or

otherwise securely tied throughout their full

height to a buttressing wall, pier or chimney.

Long walls may be provided with intermediate

buttressing walls, piers or chimneys dividing

the wall into distinct lengths within each storey;

each distinct length is a supported wall for the

purposes of this section. The intermediate

buttressing walls, piers or chimneys should

provide lateral restraint to the full height of the

supported wall, but they may be staggered at

each storey.

2C26 Buttressing Walls

If the buttressing wall is not itself a supported

wall its thickness T2 should not be less than :

Structure Approved Document A

24

A1/2 SIZES OF STRUCTURAL ELEMENTS

Standard Condition (See diagram 10) Group 1 masonry units Group 2 masonry units

Clay masonry units to A 5.0 8.0

BS EN 771-1 Calcium silicate

masonry units to BS EN 771-2 B 7.5 11.0

C 15.0 21.0

Notes:

1 Values in this Table are normalised compressive strengths (N/mm2). Compressive strengths of masonry units should be derived

according to EN 772-1.

2 The Table applies to clay and calcium silicate block masonry units where the work size exceeds 337.5mm in length or 112.5mm in

height.

3 Group 1 masonry units have not more than 25% formed voids (20% for frogged bricks). Group 2 masonry units have formed voids

greater than 25%, but not more than 55%.

Table 7 Normalised compressive strength of masonry units of clay and calcium

silicate blocks complying with BS EN 771-1 and 2 (N/mm2)

See para 2C23

a. Floor member

bearing on wall

centre line

of bearing

centre line

of bearing

b. Floor member

bearing on

joist hanger

floor span

floor

maximum 6m

floor span

maximum 6m

wall

floor

Diagram 11 Maximum span of floors

Continued on page 26

Approved Document A Structure

25

SIZES OF STRUCTURAL ELEMENTS A1/2

Retained

height

H

H should be less

than or equal to 1m

and less than or

equal to 4t

W

i)

t

Retained

height

H

H should be less

than or equal to 1m

and less than or

equal to 4t

Combined dead and

imposed load W should

not exceed 70kN/m at

base of wall.

W

iii)

t

Concrete fill

to wall cavity

Retained

height

H

H should be less

than or equal to 1m

and less than or

equal to 4(t1 + t2)

W

ii)

t1

t2

Clear wall cavity

(unfilled)

b. Maximum differences in permitted level

a. Situations where differences in level may occur

See para 2C24b

Combined dead and

imposed load W should

not exceed 70kN/m at

base of wall.

Ground

supported

floor slab

Retained

height

Suspended

ground floor

Void

To be level for

a distance of not

less than 1.25H

W

W W

H

i)

Suspended

ground floor

Retained

height

Retained

height

For value of H

see (b.) below

W

Void

ii)

iii)

Diagram 12 Differences in ground levels

Notes

1 Floor slabs in figure b have been

omitted for clarity and may be on either side

of the walls shown.

2 Cavity walls should be tied in

accordance with Table 5.

3 These recommendations apply only to

circumstances where there is a full storey

height of masonry above the upper retained

level.

a. half the thickness required by this section

for an external or separating wall of similar

height and length less 5mm, or

b. 75mm if the wall forms part of a dwelling

house and does not exceed 6m in total height

and 10m in length, and

c. 90mm in other cases.

The length of the buttressing wall should be at

least 1/6 of the overall height of the supported

wall and be bonded or securely tied to the

supporting wall and at the other end to a

buttressing wall, pier or chimney.

The size of any opening in the buttressing wall

should be restricted as shown in Diagram 13.

2C27 Design criteria for piers and chimneys

providing restraint:

a. piers should measure at least 3 times the

thickness of the supported wall and chimneys

twice the thickness, measured at right angles

to the wall. Piers should have a minimum width

of 190mm (see Diagram 14)

b. the sectional area on plan of chimneys

(excluding openings for fireplaces and flues)

should be not less than the area required for a

pier in the same wall, and the overall thickness

should not be less than twice the required

thickness of the supported wall. (see Diagram

14)

Openings, recesses, overhangs

and chases

2C28 General:

The number, size and position of openings and

recesses should not impair the stability of a

wall or the lateral restraint afforded by a

buttressing wall to a supported wall.

Construction over openings and recesses

should be adequately supported.

Structure Approved Document A

26

A1/2 SIZES OF STRUCTURAL ELEMENTS

the length of the

buttressing wall should be

at least 1/6 of the overall

height of the supported

wall

See para 2C26

an opening or recess greater

than 0.1m2 shall be at least

550mm from the supported wall

The opening height should not be more than

0.9 times the floor to ceiling height and the

depth of the lintel including any masonry

over the opening should be not less than 150mm.

buttressing

wall

there may be

one opening or

recess not more

than 0.1m2 at

any position height of

supported

wall

550mm

T2

Diagram 13 Openings in a buttressing wall

Notes

1 The buttressing wall should be bonded

or securely tied to the supported wall and at

the other end to a buttressing wall, pier or

chimney.

2 Openings or recesses in the

buttressing wall should be as shown – the

position and shape of the openings should

not impair the lateral support to be given by

the buttressing wall.

3 Refer to Diagram 8 for the rules for

measuring the height of the supported wall.

2C29 Dimensional criteria for openings and

recesses:

The dimensional criteria are given in Diagrams

15 and Table 8.

No openings should be provided in walls below

ground floor except for small holes for services

and ventilation etc. which should be limited to

a maximum area of 0.1m2 at not less than 2m

centres.

2C30 Chases:

a. vertical chases should not be deeper

than 1/3 of the wall thickness or, in cavity

walls, 1/3 of the thickness of the leaf.

b. horizontal chases should not be deeper

than 1/6 of the thickness of the leaf of the wall.

c. chases should not be so positioned as to

impair the stability of the wall, particularly

where hollow blocks are used.

2C31 Overhangs:

the amount of any projection should not impair

the stability of the wall.

Lateral support by roofs and

floors

2C32 A wall in each storey of a building should

extend to the full height of that storey, and

have horizontal lateral supports to restrict

movement of the wall at right angles to its

plane.

2C33 Floors and roofs should:

a. act to transfer lateral forces from walls to

buttressing walls, piers or chimneys, and

b. be secured to the supported wall by

connections specified in paragraphs 2C34 and

2C35.

2C34 The requirements for lateral restraint of

walls at roof and floor levels are given in Table

9 and guidance on satisfying the requirements

is given in paragraphs 2C35 and 2C36.

2C35 Walls should be strapped to floors above

ground level, at intervals not exceeding 2m and

as shown in Diagram 16 by tension straps

conforming to BS EN 845-1. For corrosion

resistance purposes, the tension straps should

be material reference 14 or 16.1 or 16.2

(galvanised steel) or other more resistant

Approved Document A Structure

27

SIZES OF STRUCTURAL ELEMENTS A1/2

the buttressing wall, pier or

chimney should provide support

to the full height of the wall

from base to top of wall

See para 2C27

centre line of

buttressing wall

centre line of pier

(alternative arrangement)

centre line

of chimney

centre line

of pier

min

190mm

see

paragraph

2C27

H

T

min 3 x T

min 3 x T

min 2 x T

Diagram 14 Buttressing

Structure Approved Document A

28

A1/2 SIZES OF STRUCTURAL ELEMENTS

See para 2C29

centre line

of butressing

wall, pier or chimney

centre line

of butressing

wall, pier or chimney

outer face of

return wall

H

should not be

greater than

2.1 m

corner of two

L = length of wall external walls

opening

W1

opening

W2

recess

P1 P2 P3 W3

opening

P4 W4 P5

Diagram 15 Sizes of openings and recesses

Span of timber Span of concrete

Span of floor

floor into wall floor into wall

Minimum is parallel max max max max

Nature of Maximum thickness of to wall 4.5m 6.0m 4.5m 6.0m

roof span roof span (m) wall inner (mm)

Value of factor ‘X’

roof spans non 100 6 6 6 6 6

parallel to wall applicable

90 6 6 6 6 5

timber roof 9 100 6 6 5 4 3

spans into wall

90 6 4 4 3 3

Table 8 Value of factor ‘x’ (see diagram 15)

Wall type Wall length Lateral support required

solid or cavity: external any length roof lateral support by every roof forming a junction with the

compartment separating supported wall

greater than 3m floor lateral support by every floor forming a junction with the

supported wall

Internal load-bearing wall (not being any length roof or floor lateral support at the top of each storey

a compartment or separating wall)

Table 9 Lateral support for walls

Notes

Requirements (refer to Table 6 or values of factor

X).

1 W1 + W2 + W3 should not exceed 2L

3

2 W1 + W2 + W3 should not exceed 3m

3 P1 should be greater than or equal to W1

X

4 P2 should be greater than or equal to W1 + W2

X

5 P3 should be greater than or equal to W2 + W3

X

6 P4 should be greater than or equal to W3

X

7 P5 should be greater than or equal to W4

but should not be less than 665mm. X

8 Take the value of the fact X from Table 6, or it

can be give the value 6, provided the

compressive strength of the bricks or blocks (in

the case of a cavity wall – in the loaded leaf) is

not less than 7N/mm2.

specifications including material references 1

or 3 (austenitic stainless steel). The declared

tensile strength of tension straps should not be

less than 8 kN.

Tension straps need not be provided:

a. in the longitudinal direction of joists in

houses of not more than 2 storeys, if the joists

are at not more than 1.2m centres and have at

least 90mm bearing on the supported walls or

75mm bearing on a timber wall-plate at each

end, and

b. in the longitudinal direction of joists in

houses of not more than 2 storeys, if the joists

are carried on the supported wall by joist

hangers in accordance with BS EN 845-1 of the

restraint type described in BS 5628: Part 1 and

shown in Diagram 16(c), and are incorporated

at not more than 2m centres, and

c. when a concrete floor has at least 90mm

bearing on the supported wall (see Diagram

16(d)), and

d. where floors are at or about the same

level on each side of a supported wall, and

contact between the floors and wall is either

continuous or at intervals not exceeding 2m.

Where contact is intermittent, the points of

contact should be in line or nearly in line on

plan. (see Diagram 16(e))

2C36 Gable walls should be strapped to roofs

as shown in Diagram 17(a) and (b) by tension

straps as described in 2C35.

Vertical strapping at least 1m in length should

be provided at eaves level at intervals not

exceeding 2m as shown in Diagram 17 (c) and

(d). Vertical strapping may be omitted if the

roof:

a. has a pitch of 15° or more, and

b. is tiled or slated, and

c. is of a type known by local experience to

be resistant to wind gusts, and

d. has main timber members spanning onto

the supported wall at not more than 1.2m

centres.

Approved Document A Structure

29

SIZES OF STRUCTURAL ELEMENTS A1/2

See para 2C35

a. Tension Strap Detail - 1 b. Tension Strap Detail - 2

c. Restraint Type Joist Hanger d. Restraint by Concrete Floor or Roof

e. Restraint of Internal Walls

Floors should be at or about the

same level on each side of the

wall

Lateral support is continuous where

joists are hard up to the wall

Where joists are not hard up to the wall

blockings at not greater than 2m centres

should be used at the same locations

on both sides of the wall

X X

X to be not less than 90mm

Joist blocked to wall

Noggings, minimum

38mm width to

extend at least 1/2

the depth of the joist

Internal leaf of external

cavity wall or internal wall

requiring lateral restraint

30 x 5mm galvanised mild

steel or other durable strap

at least 1200mm long and

held tight against masonary

wall

30 x 5mm galvanised mild

steel or other durable strap

held tight against masonary

wall and fixed across 3 joists

2m max spacing Diagram 16 Lateral support by floors

Interruption of lateral support

2C37 Where an opening in a floor or roof for a

stairway or the like adjoins a supported wall

and interrupts the continuity of lateral support,

the following conditions should be satisfied for

the purposes of Section 2C:

a. the maximum permitted length of the

opening is to be 3m, measured parallel to the

supported wall, and

b. where a connection is provided by means

other than by anchor, this should be provided

throughout the length of each portion of the

wall situated on each side of the opening, and

c. where connection is provided by mild

steel anchors, these should be spaced closer

than 2m on each side of the opening to provide

the same number of anchors as if there were

no opening, and

d. there should be no other interruption of

lateral support.

Small single-storey nonresidential

buildings and annexes

2C38 Size and proportion

(i) General

The guidance given applies in the following

circumstances:-

a. The floor area of the building or annexe

does not exceed 36m2

b. The walls are solidly constructed in

brickwork or blockwork using materials which

comply with paragraphs 2C19 to 2C22.

c. Where the floor area of the building or

annexe exceeds 10m2 the walls have a mass of

not less than 130 kg/m2.

Note: There is no surface mass limitation

recommended for floor areas of 10m2 or less.

d. Access to the roof is only for the

purposes of maintenance and repair.

e. The only lateral loads are wind loads.

Structure Approved Document A

30

A1/2 SIZES OF STRUCTURAL ELEMENTS

See para 2C36 If h is greater than 16pt, provide

restraint here at not greater

than 2 metre centres

Tension strap at highest

point that will provide a

secure connection

Tension straps at

not more than

2 metre centres

(see (b))

each joist fixed to wall-plate

with framing anchors

or shew nails

gable end wall

strap anchored to

wall and turned

over wall plate

rafter fixed to

wall-plate with

framing anchor

or truss clip

t = sum of thicknesses

of leaves + 10mm

x

h

x/2

x/2

nogging

pack

strap turned over

uncut block

strap anchored

to wall and rafter

a. Tension Strap Location

c. Vertical Strapping

at Eaves-Flat Roofs

b. Effective Strapping

at Gable Wall

d. Vertical Strapping

at Eaves-Pitched Roofs

Diagram 17 Lateral support at roof level

f. The maximum length or width of the

building or annexe does not exceed 9m.

g. The height of the building or annexe does

not exceed the lower value derived from

Diagram 2.

h. The roof is braced at rafter level,

horizontally at eaves level and at the base of

any gable by roof decking, rigid sarking or

diagonal timber bracing, as appropriate, in

accordance with BS 5268 : Part 3.

i. Walls are tied to the roof structure

vertically and horizontally in accordance with

paragraphs 2C32 to 2C36 and with horizontal

lateral restraint at roof level in accordance with

paragraph (iv) below.

j. The roof structure of an annexe is

secured to the structure of the main building at

both rafter and eaves level.

Approved Document A Structure

31

SIZES OF STRUCTURAL ELEMENTS A1/2

See para 2C38

390mm min.

390mm min.

Wall with major

openings

Isolated column

No other openings

in this zone

2.0 m

Diagram 18 Size and location of openings

Notes

1 Major opening should be restricted to

one wall only. Their aggregate width should

not exceed 5.0m and their height should not

be greater than 2.1m

2 There should be no other openings

within 2.0m of a wall containing a major

opening.

3 The aggregate size of openings in a

wall not containing a major opening should

not exceed 2.4m2.

4 There should not be more than one

opening between piers.

5 Unless there is a corner pier the

distance from a window or a door to a

corner should not be less than 390mm.

(ii) Size and location of openings

One or two major openings not more than 2.1m

in height are permitted in one wall of the

building or annexe only. The width of a single

opening or the combined width of two

openings should not exceed 5m.

The only other opening permitted in a building

or annexe are for windows and a single leaf

door. The size and location of these openings

should be in accordance with Diagram 18.

(iii) Wall thickness and recommendations for

piers

The walls should have a minimum thickness of

90mm.

Structure Approved Document A

32

A1/2 SIZES OF STRUCTURAL ELEMENTS

See para 2C38

a. Wall without a Major Opening

b. Wall with a Single Major Opening

c. Wall with Two Major Openings

Bp

Ap Ap

3.0 m max 3.0 m max 3.0 m max

90 mm min

Bp

Bp G

Ap W

Ap

Ap G

Bp

Dotted outline indicates

range of wall positions

Orientation of piers with opening width G not

greater than 2.5 m

Orientation of piers with opening width G greater

than 2.5 m

Dotted outline indicates

range of wall positions

Bp

Ap Cc

Cc

Diagram 19 Wall thickness

Notes

1 In all cases the minimum pier size (Ap

x Bp) should be 390mm x 190mm or 327mm

x 215mm depending on the size of the

masonry units.

2 Isolated column (Case c) to be 325mm

x 325mm minimum (Cc x Cc)

Walls which do not contain a major opening but

exceed 2.5m in length or height should be

bonded or tied to piers for their full height at

not more than 3m centres as shown in Diagram

19a. Walls which contain one or two major

openings should in addition have piers as

shown in Diagrams 19b and 19c. Where ties

are used to connect piers to walls they should

be flat, 20mm x 3mm in cross section, be in

stainless steel in accordance with clause 2C19,

be placed in pairs and be spaced at not more

than 300mm centre vertically.

(iv) Horizontal lateral restraint at roof level

Walls should be tied horizontally at no more

than 2m centres to the roof structure at eaves

level, base of gables and along roof slopes as

shown in Diagram 20 with straps fixed in

accordance with paragraphs 2C35 and 2C36.

Where straps cannot pass through a wall they

should be adequately secured to the masonry

using suitable fixings. Isolated columns should

also be tied to the roof structure (see Diagram

20).

Approved Document A Structure

33

SIZES OF STRUCTURAL ELEMENTS A1/2

Fixing near ridge

position

Key

denotes fixings at eaves level.

denotes fixings at base of gable.

denotes fixings along roof slope.

Note: Fixings should be in accordance with Diagram 17.

Fixing at isolated

column position

See para 2C38

Diagram 20 Lateral restraint at roof level

Height to width relationship

2D1 Where a chimney is not adequately

supported by ties or securely restrained in any

way, its height if measured from the highest

point of intersection with the roof surface,

gutter, etc. should not exceed 4.5W, provided

the density of the masonry is greater than

1500kg/m3, where:

W is the least horizontal dimension of the

chimney measured at the same point of

intersection, and

H is measured to the top of any chimney pot or

other flue terminal.(see Diagram 21)

Section 2D: Proportions for Masonry

Chimneys above the roof surface

Structure Approved Document A

34

A1/2 SIZES OF STRUCTURAL ELEMENTS

H H

W W

See para 2D1

level of highest

point of intersection

Diagram 21 Proportions for masonry

chimneys

Conditions relating to the ground

2E1 There should not be:

a. non-engineered fill (as described in BRE

Digest 427) or wide variation in ground

conditions within the loaded area, nor

b. weaker or more compressible ground at

such a depth below the foundation as could

impair the stability of the structure.

Design provisions

2E2 The following design provisions relate to

foundations:

a. the foundations should be situated

centrally under the wall

b. for foundations in chemically aggressive

soil conditions guidance in BS 8500-1 : Part 1

and BRE Special Digest 1 should be followed.

In non-aggressive soils, concrete should be

composed of Portland Cement to BS EN 197 -

1 & 2 and fine and coarse aggregate

conforming to BS EN 12620 and the mix should

comply with one of the following

recommendations:

i. in proportion of 50 kg of Portland cement

to not more than 200kg (0.1m3) of fine

aggregate and 400 kg (0.2 m3) of coarse

aggregate, or

ii. Grade ST2 or Grade GEN I concrete to

BS 8500-2

c. minimum thickness T of concrete

foundation should be 15Omm or P, whichever

is the greater where P is derived using Table 10

and Diagram 24. Trench fill foundations may be

used as an acceptable alternative to strip

foundations.

d. foundations stepped on elevation should

overlap by twice the height of the step, by the

thickness of the foundation, or 30Omm,

whichever is greater (see Diagram 22).

For trench fill foundations the overlap should

be twice the height of step or 1 metre,

whichever is greater.

e. steps in foundations should not be of

greater height than the thickness of the

foundation (see Diagram 22).

f. foundation of piers buttresses and

chimneys should project as indicated in

Diagram 23 and the projection X should never

be less than the value of P where there is no

local thickening of the wall.

Minimum width of strip

foundations

2E3 The recommended minimum widths of

foundations given in Table 10 may be used.

Section 2E: Foundations of Plain Concrete

Approved Document A Structure

35

SIZES OF STRUCTURAL ELEMENTS A1/2

See para 2E2d and e

foundations should unite at each

change in level

minimum overlap L = twice height of step, or

thickness of foundation

or 300mm, whichever is greater

S should not be greater than T

(For trench fill foundations,

minimum overlap L = twice height of step,

or 1 metre, whichever

is greater)

T

S

L

Diagram 22 Elevation of stepped

foundation

projection X should not be less than P

See para 2E2f

X

X

P

X

X

Diagram 23 Piers and chimneys

Trench fill foundations may be used as an

alternative to strip foundations.

The minimum thickness

of the foundation (T)

should either be P or

150mm, whichever is

greater

Foundation width

should be not less

than the appropriate

dimension in Table 10

See para 2E2c

Wall should be

central on foundation

P

T

W P

Diagram 24 Foundation dimensions

The table is applicable only within the strict

terms of the criteria described within it.

Minimum Depth of Strip

Foundations

2E4 Except where strip foundations are

founded on rock, the strip foundations should

have a minimum depth of 0.45m to their

underside to avoid the action of frost. This

depth however, will commonly need to be

increased in areas subject to long periods of

frost or in order to transfer the loading onto

satisfactory ground.

In clay soils subject to volume change on

drying (‘shrinkable clays’, with Plasticity Index

greater than or equal to 10%), strip foundations

should be taken to a depth where anticipated

ground movements will not impair the stability

of any part of the building taking due

consideration of the influence of vegetation and

trees on the ground. The depth to the

underside of foundations on clay soils should

not be less than 0.75m although this depth will

commonly need to be increased in order to

transfer the loading onto satisfactory ground.

Structure Approved Document A

36

A1/2 SIZES OF STRUCTURAL ELEMENTS

Total load of load-bearing walling not more than

Type of Ground

(kN/linear metre)

(including Condition Field test

20 30 40 50 60 70

engineered fill) of ground Applicable Minimum width of strip foundation (mm)

l Not inferior to Requires at least a pneumatic In each case equal to the width of wall

Rock sandstone, limestone or other mechanically operated

or firm chalk pick for excavation

ll Requires pick for excavation. 250 300 400 500 600 650

Gravel or Sand Medium dense Wooden peg 50mm square in cross

section hard to drive beyond 150mm

lll Can be indented slightly by thumb 250 300 400 500 600 650

Clay Stiff

Sandy Clay Stiff

lV Thumb makes impression easily 300 350 450 600 750 850

Clay Firm

Sandy Clay Firm

V Can be excavated with a spade. 400 600

Sand Loose Wooden peg 50mm square in

Silty sand Loose cross section can be easily driven

Clayey sand Loose

Vl Finger pushed in up to 10mm 450 650

Silt Soft

Clay Soft

Sandy clay Soft

Clay or silt Soft

Vll Finger easily pushed in up to 25mm Refer to specialist advice

Silt Very soft

Clay Very soft

Sandy clay Very soft

Clay or silt Very soft

Table 10 Minimum width of strip footings

Note

Foundations on soil types V

and V1 do not fall within the

provisions of this section if the

total load exceeds 30 kN/m.

General

3.1 Wall cladding presents a hazard if it

becomes detached from the building. This

Section provides guidance on the support and

fixing of wall cladding. An acceptable level of

safety can be achieved by different means

depending on the type and location of the

cladding. The guidance given relates to all

forms of cladding, including curtain walling and

glass facades. It is not intended to provide

guidance concerning the weather resistance of

wall cladding which is included in Approved

Document C Site preparation and resistance to

moisture, or guidance on resistance to spread

of fire which is included in Approved Document

B, Fire Safety, or guidance in relation to sound

insulation, which is included in Approved

Document E, Resistance to the Passage of

Sound.

Technical Approach

3.2 The cladding will meet the safety

requirement if:

a. the cladding is capable of safely

sustaining and transmitting to the supporting

structure of the building all dead, imposed and

wind loads, and

b. the cladding is securely fixed to and

supported by the structure of the building. This

shall comprise both vertical support and

horizontal restraint, and

c. provision is made, where necessary, to

accommodate differential movement of the

cladding and the supporting structure of the

building, and

d. the cladding and its fixings (including any

support components) are of durable materials;

the design life of the fixings being not less than

that of the cladding. Fixings shall be corrosion

resistant and of a material type appropriate for

the local environment.

Loading

3.3 Wind loading on the cladding should be

derived from BS 6399, Part 2: 2001 with due

consideration given to local increases in wind

suction arising from funnelling of the wind

through gaps between buildings. Guidance on

funnelling effects is given in BRE Digest 436

Wind loading on buildings - Brief guidance for

using BS 6399-2: 1997 available from BRE,

Bucknalls Lane, Garston, Watford, Herts WD2

7JR.

3.4 Where the cladding is required to support

other fixtures e.g. handrails, and fittings, e.g.

antennae and signboards, account should be

taken of the loads and forces arising from such

fixtures and fittings.

3.5 Where the wall cladding is required to

function as pedestrian guarding to stairs,

ramps, vertical drops of 600mm or greater or

as a vehicle barrier, then account should be

taken of the additional imposed loading, as

stipulated in Approved Document K: Protection

from failing, collision and impact.

3.6 Where the wall cladding is required to

safely withstand lateral pressures from crowds,

an appropriate design loading is given in BS

6399 Part 1 and the Guide to Safety at Sports

Grounds (4th Edition, 1997).

Fixings

3.7 The selection of fixings for supporting

cladding should be determined from a

consideration of the proven performance of the

fixing and the risks associated with the

particular application. In this regard

applications should be designated as being

either non-redundant (where the failure of a

single fixing could lead to the detachment of

the cladding) or redundant (where failure or

excessive movement of one fixing results in

load sharing by adjacent fixings) and the

required reliability of the fixing determined

accordingly.

Note: Attention is drawn to the availability of

anchors with an ETA (European Technical

Approval) gained in accordance with the

requirements of ETAG 001 Guideline for

European Technical Approval Metal Anchors for

use in Concrete Parts 1-5, which cover both

redundant and non-redundant applications, and

Part 6 which covers “Anchors for multiple use

in non-structural applications” and which can

effectively be regarded as covering redundant

use. The UK definition of “Multiple use” is

contained in an annex to the ETAG Part 6 and

is framed in such a way that all applications

can be validated as to whether or not they

conform to this category without calculation.

All ETAG parts may be downloaded in English

from www.eota.be.

3.8 The strength of fixings should be derived

from tests using materials representative of the

material into which the fixing is to be anchored,

taking account of any inherent weaknesses that

may affect the strength of the fixing, eq. cracks

in concrete due to shrinkage and flexure, or

voids in masonry construction. The design

loads will generally be available from the

manufacturer’s test data determined from a

European Technical Approval (ETA) or an extant

British Standard

Note: ETAS are available which cover use either

in both cracked and non-cracked concrete or in

non-cracked concrete only. Those which cover

both cracked and non-cracked concrete allow

higher loads for use in non-cracked than in

cracked concrete. Guidance on how to

Section 3: Wall Cladding

Approved Document A Structure

37

WALL CLADDING A1/2

determine whether a particular concrete

section may be regarded as cracked or noncracked

without reverting to stress calculations

is contained in “Use of anchors with European

Technical Approvals. UK Guidance - Distinction

between cracked and non-concrete concrete”.

This is available on the BBA website

www.bbacerts.co.uk click tab “ETA”.

Further Guidance

3.9 The use of large panels of glass in

cladding of walls and roofs where the cladding

is not divided into small areas by load bearing

framing requires special consideration.

Guidance is given in the following documents:

The Institution of Structural Engineers’ Report

on ‘Structural use of glass in buildings’ dated

1999, available from 11 Upper Belgrave Street,

London SW1X 8BH.

‘Nickel sulfide in toughened glass’ published

by the Centre for Window Cladding and

Technology dated 2000.

3.10 Further guidance on cladding is given in

the following documents -

The Institution of Structural Engineers’ Report

on ‘Aspects of Cladding’ dated 1995.

The Institution of Structural Engineers’ Report

on ‘ Guide to the structural use of adhesives’

dated 1999.

BS 8297 Code of practice for the design and

installation of non-load bearing precast

concrete cladding.

BS 8298 Code of practice for the design and

installation of natural stone cladding and lining.

3.11 Additional guidance on fixings is given in

the following documents -

ETAG No. 001 1997 Guideline for European

Technical Approvals of Metal Anchors for use in

Concrete, European Organisation for Technical

Approvals, (EOTA) Brussels. All EOTA parts may

be downloaded in English from www.eota.be

English version published by the British Board

of Agreement, P 0 Box 195, Bucknalls Lane,

Garston, Watford, Hertfordshire WD25 9BA.

Part 1 Anchors in general

Part 2 Torque controlled anchors

Part 3 Undercut anchors

Part 4 Deformation controlled anchors

Part 5 Bonded anchors

Part 6 Metal anchors for redundant use in

concrete for lightweight systems.

BS 5080 Structural fixings in concrete and

masonry Part 1 1993 : Method of test for

tensile loading.

CIRIA Report RP 566 Cladding Fixings : Good

practice guidance, available from 6 Storey’s

Gate, London SWIP 3AU

CIRIA Reports C579 and C589 Retention of

masonry facades - Best practice guide.

Guidance Notes published by the Construction

Fixings Association, c/o Institute of Spring

Technology, Henry Street, Sheffield, South

Yorks S3 7EQ

Guidance Note: Procedure for Site Testing

Construction Fixings (1994)

Guidance Note: European Technical Approvals

for Construction Fixings (1998)

Guidance Note Anchor Selection (1995)

Guidance Note Fixings and Fire (1998)

Guidance Note: Anchor Installation (1996)

Guidance Note: Bonded Anchors (1999)

Guidance Note: Heavy Duty Expansion Anchors

(1997)

Guidance Note: Fixings for Brickwork and

Blockwork (1997)

Guidance Note: Undercut Anchors (1998)

Guidance Note: Fixings and Corosion (2002)

Structure Approved Document A

38

A1/2 WALL CLADDING

Materials

4.1 All materials used to cover roofs, including

transparent or translucent materials, but

excluding windows of glass in residential

buildings with roof pitches of not less than 15°,

shall be capable of safely withstanding the

concentrated imposed loads upon roofs

specified in BS 6399 pt 3.

Recovering of Roofs

4.2 The recovering of roofs is commonly

undertaken to extend the useful life of

buildings. Roof structures may be required to

carry underdrawing or insulation provided at a

time later than their initial construction. This

Section provides guidance on determining

whether such work to a roof constitutes a

material alteration under the Building

Regulations.

4.3 Where the work involves a significant

change in the applied loading the structural

integrity of the roof structure and the

supporting structure should be checked to

ensure that upon completion of the work the

building is not less compliant with requirement

A1 than that of the original building.

4.4 A significant change in roof loading is

when the loading upon the roof is increased by

more than 15%.

4.5 Where such checking of the existing roof

structure indicates that the construction is

unable to sustain any proposed increase in

loading (e.g. due to overstressed members or

unacceptable deflection leading to ponding),

appropriate strengthening work or replacement

of roofing members should be undertaken. This

is classified as a material alteration.

4.6 In carrying out the checks mentioned in

paragraph 4.3 an increase of stress in a

structural member arising from increased

loading does not necessarily indicate that the

roof structure is less compliant than the

original roof provided an adequate factor of

safety is maintained.

4.7 Where work will significantly decrease the

roof dead loading, the roof structure and its

anchorage to the supporting structure should

be checked to ensure that an adequate factor

of safety is maintained against uplift of the roof

under imposed wind loading.

Section 4: Roof Covering

Approved Document A Structure

39

ROOF COVERING A1/2

This Approved Document deals with the

following Requirements which are contained in

the Building Regulations 2000 (as amended by

SI 2001/3335, SI 2002/440, SI 2002/2871 and

SI 2003/2692.

The Requirement

Structure Approved Document A

40

A3 DISPROPORTIONATE COLLAPSE

Disproportionate Collapse

A3. The building shall be constructed so that in the event of an accident

the building will not suffer collapse to an extent disproportionate to the

cause.

Requirement Limits on application

Performance

In the Secretary of State’s view the

Requirement of A3 will be met by an

appropriate choice of measures to reduce the

sensitivity of a building to disproportionate

collapse should an accident occur.

Introduction

0.1 The guidance in Section 5 deals with the

means of meeting this performance criterion.

Guidance

Approved Document A Structure

41

DISPROPORTIONATE COLLAPSE

5.1 The requirement will be met by adopting

the following approach for ensuring that the

building is sufficiently robust to sustain a

limited extent of damage or failure, depending

on the class of the building, without collapse.

a. Determine the Building Class from Table

11

b. For Class 1 buildings - Provided the

building has been designed and constructed in

accordance with the rules given in this

Approved Document, or other guidance

referenced under Section 1, for meeting

compliance with requirement A1 and A2 in

normal use, no additional measures are likely

to be necessary.

c. For Class 2A buildings - Provide

effective horizontal ties, or effective anchorage

of suspended floors to walls, as described in

the Codes and Standards listed under

paragraph 5.2 for framed and load-bearing wall

construction; the latter being defined in

paragraph 5.3 below.

d. For Class 2B buildings - Provide

effective horizontal ties, as described in the

Codes and Standards listed under paragraph

5.2 for framed and load-bearing wall

construction; (the latter being defined in

paragraph 5.3 below), together with:

– effective vertical ties, as defined in the

Codes and Standards listed under

Section 5: Reducing the sensitivity of the

building to disproportionate collapse in the

event of an accident

Structure Approved Document A

42

A3 DISPROPORTIONATE COLLAPSE

Class Building Type and Occupancy

1 Houses not exceeding 4 storeys.

Agricultural buildings

Buildings into which people rarely go, provided no part of the building is closer to another building, or area where

people do go, than a distance of 1.5 times the building height

2A 5 storey single occupancy houses

Hotels not exceeding 4 storeys

Flats, apartments and other residential buildings not exceeding 4 storeys

Offices not exceeding 4 storeys

Industrial buildings not exceeding 3 storeys

Retailing premises not exceeding 3 storeys of less than 2000m2 floor area in each storey

Single storey educational buildings

All buildings not exceeding 2 storeys to which members of the public are admitted and which contain floor areas not

exceeding 2000m2 at each storey

2B Hotels, flats, apartments and other residential buildings greater than 4 storeys but not exceeding 15 storeys

Educational buildings greater than 1 storey but not exceeding 15 storeys

Retailing premises greater than 3 storeys but not exceeding 15 storeys

Hospitals not exceeding 3 storeys

Offices greater than 4 storeys but not exceeding 15 storeys

All buildings to which members of the public are admitted which contain floor areas exceeding 2000m2 but less than

5000m2 at each storey

Car parking not exceeding 6 storeys

3 All buildings defined above as Class 2A and 2B that exceed the limits on area and/or number of storeys

Grandstands accommodating more than 5000 spectators

Buildings containing hazardous substances and/or processes

NOTE 1: For buildings intended for more than one type of use the Class should be that pertaining to the most onerous type.

NOTE 2: In determining the number of storeys in a building, basement storeys may be excluded provided such basement storeys

fulfil the robustness requirements of Class 2B buildings.

Table 11 Building Classes

paragraph 5.2, in all supporting columns

and walls, or alternatively,

– check that upon the notional removal of

each supporting column and each beam

supporting one or more columns, or any

nominal length of load-bearing wall (one

at a time in each storey of the building)

that the building remains stable and that

the area of floor at any storey at risk of

collapse does not exceed 15% of the

floor area of that storey or 70m2,

whichever is smaller, and does not

extend further than the immediate

adjacent storeys (see Diagram 25).

Where the notional removal of such columns

and lengths of walls would result in an extent

of damage in excess of the above limit, then

such elements should be designed as a “key

element” as defined in paragraph 5.3 below.

e. For Class 3 buildings - A systematic risk

assessment of the building should be

undertaken taking into account all the normal

hazards that may reasonably be foreseen,

together with any abnormal hazards.

Critical situations for design should be selected

that reflect the conditions that can reasonably

be foreseen as possible during the life of the

building. The structural form and concept and

any protective measures should then be

chosen and the detailed design of the structure

and its elements undertaken in accordance

with the recommendations given in the Codes

and Standards given in paragraph 5.2.

5.2 Details of the effective horizontal and

vertical ties, together with the design

approaches for checking the integrity of the

building following the notional removal of

vertical members and the design of key

elements, are available in the following Codes

and Standards:

BS5628: Part 1 – Structural use of unreinforced

masonry

BS5950: Part 1 – Structural use of steelwork

in building

BS8110: Part 1 – Structural use of plain,

reinforced and prestressed concrete.

BS8110: Part 2 – ditto

5.3 Definitions

Nominal length of load-bearing wall

The nominal length of load-bearing wall

construction referred to in 5.1d should be

taken as follows :

– in the case of a reinforced concrete wall,

the distance between lateral supports

subject to a maximum length not

exceeding 2.25H.

– in the case of an external masonry wall,

or timber or steel stud wall, the length

measured between vertical lateral

supports.

– in the case of an internal masonry wall, or

timber or steel stud wall, a length not

exceeding 2.25H.

– where H is the storey height in metres.

Key Elements

A “key element”, as referred to in paragraph

5.1d, should be capable of sustaining an

accidental design loading of 34 kN/m2 applied

in the horizontal and vertical directions (in one

direction at a time) to the member and any

attached components (eg cladding etc.) having

regard to the ultimate strength of such

components and their connections. Such

accidental design loading should be assumed

to act simultaneously with 1/3 of all normal

characteristic loading (i.e. wind and imposed

loading).

Load-bearing Construction

For the purposes of this Guidance the term

“load-bearing wall construction” includes

masonry cross-wall construction and walls

comprising close centred timber or lightweight

steel section studs.

Alternative Approach

5.4 Alternatively, for any building which does

not fall into the classes listed under Table 11 or

for which the consequences of collapse may

warrant particular examination of the risks

involved, the performance may be met by the

recommendations given in the following

Reports:

“Guidance on Robustness and Provision

against Accidental Actions” dated July,1999,

together with the accompanying BRE Report

No. 200682

“Calibration of Proposed Revised Guidance on

meeting Compliance with the Requirements of

Building Regulation Part A3.

Both of the above documents are available on

the following ODPM web-site

http://www.odpm.gov.uk

Approved Document A Structure

43

DISPROPORTIONATE COLLAPSE A3

Structure Approved Document A

44

A3 DISPROPORTIONATE COLLAPSE

area at risk of collapse

limited to 15% of the

floor area of that storey

or 70m2, whichever is

the less, and does not

extend further than the

immediate adjacent

storeys.

Plan Section

See para 5.1d

Diagram 25 Area at risk of collapse in the event of an accident

A1/2

BS 187 : 1978 Specification for calcium

silicate (sandlime and

flintlime) bricks

Amendment slip

1. AMD 5427

BS 1243:1978 Specification for metal ties for

cavity wall construction

Amendment slips

1. AMD 3651

2. AMD 4024

BS 3921:1985 Specification for clay bricks

Amendment slip

1. AMD 8946

BS 5080: Structural fixings in concrete

and masonry

Part 1 : 1993 Method of test for tensile

loading

BS 5268: Structural use of timber

Part 2: 2002 Code of practice for

permissible stress design,

materials and workmanship

Part 3: 1998 Code of practice for trussed

rafter roofs.

BS 5390:1976 Code of practice for stone

masonry

Amendment slip

1. AMD 4272

BS 5628: Code of practice for use of

masonry

Part 1: 1992 Structural use of unreinforced

masonry

Amendment slip

1. AMD 7745

2. AMD 13680

Part 2: 2000 Structural use of reinforced

and prestressed masonry

Part 3: 2001 Materials and components,

design and workmanship

BS 5950: Structural use of steelwork in

building

Part 1: 2000 Code of practice for design.

Rolled and welded sections.

Amendment slip

1. AMD 13199

Part 2:2001 Specification for materials,

fabrication and erection.

Rolled and welded sections.

Part 3 : Design in composite

construction

Section 3.1: 1990 Code of practice for design

of simple and continuous composite beams.

Part 4: 1994 Code of practice for design of

composite slabs with profiled

steel sheeting.

Part 5: 1998 Code of practice for design of

cold formed thin gauge

sections.

BS 6073: Precast concrete masonry

units

Part 1: 1981 Specification for precast

concrete masonry units

Amendment slips

1. AMD 3944

2. AMD 4462

BS 6399: Loading for buildings :

Part 1: 1996 Code of practice for dead and

imposed loads

Amendment slip

1. AMD 13669

BS 6399: Loading for buildings :

Part 2: 1997 Code of practice for wind

loads

Amendment slip

1. AMD 13392

2. AMD 14009

BS 6399: Loading for buildings

Part 3 :1988 Code of practice for imposed

roof loads.

Amendment slip

1. AMD 6033

2. AMD 9187

3. AMD 9452

BS 6649: 1985 Specification for clay and

calcium silicate modular

bricks

BS 8002: 1994 Code of practice for earth

retaining structures

BS 8004: 1986 Code of practice for

foundations.

Amendment slip

1. AMD 8851

2. AMD 12062

3. AMD 13386

BS 8103: Structural design of low-rise

buildings :

Part 1: 1995 Code of practice for stability,

site investigation, foundations

and ground floor slabs for

housing.

Amendment slip

1. AMD 8980

Part 2: 1996 Code of practice for masonry

walls for housing

Part 3: 1996 Code of practice for timber

floors and roofs for housing.

Part 4: 1995 Code of practice for

suspended concrete floors for

housing

BS 8110: Structural use of concrete

Part 1: 1997 Code of practice for design

and construction

Amendment slip

1. AMD 9882

2. AMD 13468

Approved Document A Structure

45

STANDARDS REFERRED TO A

Part 2: 1985 Code of practice for special

circumstances

Amendment slip

1. AMD 5914

2. AMD 12061

Part 3: 1995 Design charts for singly

reinforced beams, doubly

reinforced beams and

rectangular columns.

Amendment slip

1. AMD 5918

BS 8118: Structural use of aluminium

Part 1: 1991 Code of practice for design

Amendment slip

1. AMD 10485

Part 2: 1991 Specification for materials,

workmanship and protection

Amendment slip

1. AMD 10486

BS 8297: 2000 Code of practice for design

and installation of nonloadbearing

precast concrete

cladding.

Amendment slip

1. AMD 11064

2. AMD 13018

BS 8298: 1994 Code of practice for design

and installation of natural

stone cladding and lining

BS 8500: Concrete. Complementary

British Standard to BS EN

206-1

Part 1:2002 Method of specifying and

guidance for the specifier

Part 2:2002 Specification for constituent

materials and concrete

BS EN 197 Cement

Part 1:2000 Composition, specifications

and conformity criteria for

common elements

Part 2:2000 Conformity evaluation

BS EN 771 Specification for Masonry

Units

Part 1 :2003 Clay masonry units

Part 2 :2001 Calcium silicate masonry

units

Part 3 : Aggregate concrete masonry

units [in preparation]

Part 4 : 2001 Autoclaved aerated concrete

masonry units

Part 5 : Manufactured stone masonry

units [in preparation]

Part 6 : 2001 Natural stone masonry units

BS EN 845 Specification for ancillary

components for masonry

Part 1 : 2001 Ties, tension straps, hangers

and brackets

Part 2 : 2001 Lintels

Part 3 : 2001 Bed joint reinforcement of

steel meshwork

BS EN 998 Specification for mortar for

masonry

Part 2 :2002 Masonry mortar

BS EN 12620: Aggregates for concrete

2002

DD140-1: 1986 Method of test for mortar joint

and timber frame connections

DD140-2: 1987 Recommendations for design

of wall ties

A3

BS 5628: Code of practice for use of

masonry

Part 1: 1992 Structural use of unreinforced

masonry

Amendment slip

1. AMD 7745

2. AMD 13680

BS 5950: Structural use of steelwork in

building

Part 1: 2000 Code of practice for design.

Rolled and welded sections.

Amendment slip

1. AMD 13199

BS 8110: Structural use of concrete

Part 1: 1997 Code of practice for design

and construction

Amendment slip

1. AMD 9882

2. AMD 13468

Part 2: 1985 Code of practice for special

circumstances

Amendment slip

1. AMD 5914

2. AMD 12061

Structure Approved Document A

46

STANDARDS REFERRED TO

The following documents have been approved

and issued by the Secretary of State for the

purpose of providing practical guidance with

respect to the requirements of the Building

Regulations 2000 (as amended).

Approved Document A – Structure: 2004

Edition

Approved Document B – Fire safety: 2000

Edition, amended 2000 and 2002

Approved Document C – Site preparation and

resistance to moisture: 1992 Edition, second

impression (with amendments) 1992, further

amended 2000

Approved Document D – Toxic substances:

amended 1992, further amended 2000

Approved Document E – Resistance to the

passage of sound: 2003 Edition

Approved Document F – Ventilation: 1995

Edition, amended 2000

Approved Document G – Hygiene: 1992

Edition, second impression (with amendments)

1992, further amended 2000

Approved Document H – Drainage and waste

disposal: 2002 Edition

Approved document J – Combustion

appliances and fuel storage systems:

2002 Edition

Approved Document K – Protection from

falling, collision and impact: 1998 Edition,

amended 2000

Approved document L1 – Conservation of fuel

and power in dwellings: 2002 Edition

Approved document L2 – Conservation of fuel

and power in buildings other than dwellings:

2002 Edition

Approved Document M – Access and facilities

for disabled people: 2004 Edition

Approved Document N – Glazing - safety in

relation to impact, opening and cleaning: 1998

Edition, amended 2000

Approved Document to support regulation 7

– materials and workmanship: 1999 Edition,

amended 2000

Approved Document A Structure

47

Approved Documents

APPROVED DOCUMENTS

Building Regulations 2000 APPROVED DOCUMENT A Structure

© Crown Copyright 2004.

Copyright in the typographical arrangement and design rests with the Crown.

Published for the Office of the Deputy Prime Minister, under licence from the Controller of Her Majesty’s Stationery Office.

This publication, excluding logos, may be reproduced free of charge in any format or medium for research, private study or for internal circulation within an

organisation.This is subject to it being reproduced accurately and not used in a misleading context.The material must be acknowledged as Crown copyright

and the title of the publication specified.

For any other use of this material please write to The HMSO Licensing Division, HMSO, St Clements House, 2–16 Colegate, Norwich NR3 1BQ.

Fax: 01603 723000 or email: licensing@cabinet-office.x.gsi.gov.uk

£11

www.tso.co.uk

Published by TSO (The Stationery Office) and available from:

Online

www.tso.co.uk/bookshop

Mail,Telephone, Fax & E-mail

TSO

PO Box 29, Norwich NR3 1GN

Telephone orders/General enquiries: 0870 600 5522

Fax orders: 0870 600 5533

E-mail: book.orders@tso.co.uk

Textphone: 0870 240 3701

TSO Shops

123 Kingsway, London WC2B 6PQ

020 7242 6393 Fax 020 7242 6394

68–69 Bull Street, Birmingham B4 6AD

0121 236 9696 Fax 0121 236 9699

9–21 Princess Street, Manchester M60 8AS

0161 834 7201 Fax 0161 833 0634

16 Arthur Street, Belfast BT1 4GD

028 9023 8451 Fax 028 9023 5401

18–19, High Street, Cardiff CF10 1PT

029 2039 5548 Fax 029 2038 4347

71 Lothian Road, Edinburgh EH3 9AZ

0870 606 5566 Fax 0870 606 5588

TSO Accredited Agents

(see Yellow Pages)

and through good booksellers